Easypact CVS - CVS100B TM25D circuit breaker - 4P/3d

      











LV510311
Easypact CVS - CVS100B TM25D circuit breaker - 4P/3d

Characteristics
Main
Range of product Easypact CVS100...250
Product or component type Circuit breaker
Device short name CVS100B
Device application Distribution
Poles description 4P
Protected poles description 3d
Neutral position Left
Earth leakage protection (Vigi add on) Without
[In] rated current 100 A ( 40 °C )
Breaking capacity code B
Network type AC
[Ue] rated operational voltage 440 V AC conforming to EN/IEC 60947-2 50/60 Hz
[Icu] Breaking capacity 40 kA Icu conforming to IEC 60947-2 at 220/240 V AC 50/60 Hz
20 kA Icu conforming to IEC 60947-2 at 440 V AC 50/60 Hz
25 kA Icu conforming to IEC 60947-2 at 380/415 V AC 50/60 Hz
Utilisation category Category A
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 25 A ( 40 °C )
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Complementary
Network frequency 50/60 Hz
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
[Ui] rated insulation voltage 690 V conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity 15 kA conforming to IEC 60947-2 440 V AC 50/60 Hz
25 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz
40 kA conforming to IEC 60947-2 220/240 V AC 50/60 Hz
Mechanical durability 30000 cycles
Electrical durability 12000 cycles conforming to IEC 60947-2 415 V In
Connection pitch 35 mm
Contact position indicator Yes
Neutral protection setting No protection 3d
Long time pick-up adjstment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Ii Fixed
Instantaneous pick-up adjustment range 300 A
Height 161 mm
Width 140 mm
Depth 86 mm
Environment
Electrical shock protection class Class II
Standards EN 60947-2
IEC 60947-2
Product certifications GOST
IEC
Pollution degree 3 conforming to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Offer Sustainability
Sustainable offer status Not Green Premium product
RoHS (date code: YYWW) Compliant - since 1041 - print Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available printDownload Product environmental